0

75 kVA / 82.5 kVA / 100 kVA / 125 kVA Print Diesel Generator Set

75 kVA / 82.5 kVA / 100 kVA / 125 kVA Print Diesel Generator Set
Product Description

Technical Specifications :

Genset Rating (kVA)

75

82.5

100

125

Power Rating (kW)

60

66

80

100

No. of Phases

3 Phase

3 Phase

3 Phase

3 Phase

Output Voltage (V)

415V

415V

415V

415V

Power Factor (lagging)

0.8

0.8

0.8

0.8

Current (A) (1phase / 3 phase)

104

115

139

174

Frequency (Hz) RPM

50/1500

50/1500

50/1500

50/1500

Governing Class

A1

A1

A1

G2 as per ISO 8528 part V

Starting system

12V DC Electrical

12V DC Electrical

12V DC Electrical

24V DC Electrical

Fuel tank capacity (lit)

230

200

200

219

Genset dimensions (L x W x H) (mm) approx

3000x1150x2135

3200x1200x1600

3200x1200x1600

3750x1030x1500

Genset weight (kg)

1350

1700

1750

1900

Engine Specifications :

Make

Mahindra

Mahindra mPowder

Model

41035GMC2

Mpowder

41015G

Mpowder 41265G

Mpower 61565G

Power Output (HP)

103

101

126

156

Aspiration

TCI

TCA

TCA

TCA

No. of cylinders

4

4

4

6

Bore x Stroke (mm)

96x122

105x137

105x137

105x137

Displacement (cc)

3.5

4.8

4.8

7.2

Fuel consumption @ 75% load (lit/hr)

13.5

13.9

17.3

21.4

Fuel consumption @ 100% load (lit/hr)

17.8

18.1

23.1

28

Lube oil specification

SAE 15w 40 CI4

15W40 API CI4

15W40 API CI4

15W40 APICI4

Total lube oil system capacity (liter)

10

13.5

13.5

20.2

Lube oil consumption (lit/hr)°

0.15% of Fuel Consumption

0.1% of Fuel Consumption

Lube oil change period (hrs.)

300 hrs. for oil top up, 600 hrs for oil change

500 hrs. for oil change

Radiator coolant capacity (liters)

19

19

19

22.5

Alternator Specifications

Make

Mahindra Powerol

Enclosure Type

IP23

IP23

IP23

IP23

Voltage regulation

+1%

+1%

+1%

+1%

Class of insulation

Class H

Class H

Class H

Class H

Maximum Unbalanced Load across Phases

25%

25%

25%

25%

Notes :

  • Above specifications are subject to change without prior notice due to continuous product improvement
  • All Engines & alternators conform to respective IS standards
  • All the genset specifications conform to ISO 8528 Standard
  • height without sliencer
  • Fuel- High speed Diesel (HSO IS 1460 : 2005)
  • Considering 0.845 specific gravity of diesel, 5% tolerance
  • $Considering 0.89 specific gravity of oil.
  • All specifications are at standard NTP operating conditions
  • Engine power output 110% load.
Contact Us

Shop No. 15, K. P. Complex, Barve Compound, Navapur Road, Boisar, Maharashtra, 401501, India
Phone :+918068216888