Price And Quantity
    Product Specifications
    • 5950*2000*2350 Millimeter (mm)
    • 350 Liter (L)
    • 4-stroke
    • 65.5 Liter/Hour (L/hr)
    • 130*157
    • Diesel generator
    • 230V/415V Volt (V)
    • Electric Start
    • 50 Hertz (HZ)
    • Red
    • WATER COOLED
    • <75 db
    • Three Phase
    • 1500 RPM
    • 7500 Kilograms (kg)
    • 2
      Product Description

      Technical Specifications :

      Genset Specifications :

      Genset Prime Rating (kVA)

      400

      500

      625

      Genset Prime Rating (KW)

      320

      400

      500

      Phase / Voltage (V)

      3/415

      Power Factor

      0.8 (lagging)

      Current (A)

      556

      695

      868

      Frequency (Hz)& RPM

      50/1500

      Governing class

      G2 as per ISO 8528 Part V

      G2 as per ISO 8528 Part V

      G2 as per ISO 8528 Part V

      Starting system

      24 V DC Elec

      Fuel tank capacity (lit)

      900

      Canopy dimensions w/o silencer (mm) (L x W x H) approx.

      5950x2000x2350

      Genset Weight (kg) approx.

      5950

      6500

      7500

      Engine Specification

      Make / Series

      Perkins

      Engine Model

      2206D-E13TAG3

      2506D-E15TAG2

      2806D-E18TAG 1A

      Rated Power at 100% Load @ 1500 RPM (HP)

      367

      453

      540

      Aspiration

      Turbo Charged After Cooled

      No. of cylinders

      6

      Bore x Stroke (mm)

      130*157

      137*171

      145*183

      Displacement (Lit)

      12.5

      15.2

      18.1

      Fuel consumption @ 75% load (lit/hr)

      65.5

      78.6

      97

      Fuel consumption @ 100% load (lit/hr)

      90.5

      101

      130

      Total lubrication system capacity (lit)

      40

      62

      71

      Lube oil consumption @ 100% load

      0.1% of fuel consumption

      Lube oil change period (hrs.)

      500

      Radiator Coolant capacity (lit)

      51.4

      48

      55.6

      Alternator Specifications :

      Enclosure Type

      IP23

      Voltage regulation

      +1%

      Class of insulation

      Class H

      Maximum Unbalanced Load across Phases

      25%

      Note :

      Above specifications are subject to change without prior notice due to continuous product improvements. All engines & alternators confirm to respective IS standards. All the genset specifications are as per ISO 8528 standard. Fuel - High Speed Diesel (HSD IS 1460:2005) Considering 0.845 specific gravity of diesel 5% tolerance. Considering 0.89 specific gravity of oil. For Standby duty, contact Powerol authorized representative. All specifications are at standard NTP operating conditions. All the above gensets conform to the latest CPCB norms of <75 dbA

      Trade Information
      • mumbai
      • Others, Cheque, Cash in Advance (CID), Cash Advance (CA), Cash on Delivery (COD), Cash Against Delivery (CAD)
      • Maharashtra
      Contact Us

      Shop No. 15, K. P. Complex, Barve Compound, Navapur Road, Boisar, Maharashtra, 401501, India
      Phone :+918068216888